Measurement line |
Single-phase, Three-phase (should be balanced and no distortion) |
Measurement items |
Voltage, Current, Voltage/current
peak, Active/ reactive/ apparent power, Power factor, Phase angle,
Reactivity, Frequency, Voltage/current harmonic levels |
Voltage ranges
30 - 1kHz |
150.0 V to 600 V, 3 ranges
Basic accuracy: ±1.0 % rdg. ±3 dgt. (at 45 - 66 Hz, True RMS) |
Current ranges
45 - 1kHz |
20.00 A to 1000 A, 3 ranges
Basic accuracy: ±1.3 % rdg. ±3 dgt. (at 45 - 66 Hz, True RMS) |
Power ranges
80 - 600 V
1 - 1000 A |
[Single phase] 3.000 kW to 600.0 kW
Basic accuracy: ±2.3 % rdg. ±5 dgt. (at 50/60 Hz, Power factor = 1)
[Balanced three phase] 6.000 kW to 1200 kW
Basic accuracy: ±3.0 % rdg. ±10 dgt. (at 50/60 Hz, Power factor = 1) |
Harmonic levels |
Voltage/current harmonic levels up to 20th, Content factor, Total harmonic distortion ratio |
Other function |
[Phase angle] Forward 90.0° to 0 to delay 90.0°
[Power factor] Forward 0 to 1.000 to delay 0
[Frequency] 30.0 Hz to 1000 Hz
Waveform peak, Phase detection, Max. / Min. value record, Data
hold, Auto-power off, RS-232C output (Options are discontinued, so
cannot use RS-232C) |
Display |
LCD, Max. 6000 digits, Display refresh rate: 1 time/s (Normal) 1 time/3sec (Slow), 1 time/2sec (Harmonic level) |
Power supply |
Stacked alkaline battery (6LR61, 6LF22) ×1, Continuous use: 25 hours |
Core jaw dia. |
φ 55 mm (2.17 in) or 80 mm (3.15 in) × 20 mm (0.79 in) busbar |
Dimensions, mass |
100 mm (3.94 in) W × 287 mm (11.3 in) H × 39 mm (1.54 in) D, 650 g (22.9 oz) |
Supplied accessories |
CARRYING CASE 9245 ×1, VOLTAGE CORD L9635-01 ×1, Hand strap ×1, Dry cell battery (6LF22) ×1, Instruction Manual ×1 |